KL6781 | M-Bus master terminal
The KL6781 M-Bus master terminal enables the direct connection of M-Bus devices. The M-Bus (Meter Bus) is a fieldbus for the acquisition of consumption data from electricity, water, gas or energy meters. The KL6781 does not contain the M-Bus protocol; instead, it converts the data present on the terminal bus into M-Bus compliant physics. 24 byte data are available on the K-bus for this. In conjunction with the TwinCAT M-Bus library, it is possible to work without an external M-Bus gateway, i.e. the M-Bus devices can be connected directly to the KL6781. With a total cable length of 300 m, up to 40 M-Bus devices (each with a current consumption of 1.5 mA) can be connected.
| Technical data |
KL6781 |
| Technology |
M-Bus |
| Data transfer channels |
1 |
| M-Bus devices |
max. 40 each with a current consumption of 1.5 mA |
| Data transfer standard |
M-Bus physics |
| Data transfer rates |
300…9,600 baud (default 2,400 baud) |
| Bus access |
master-slave mode (polling) |
| Cable length |
max. 300 m |
| Current consumpt. K-bus |
typ. 65 mA |
| Current consumption power contacts |
max. 250 mA |
| Short-circuit-proof |
yes |
| Electrical isolation |
500 V (K-bus/M-Bus) |
| Bit width in the process image |
input/output: 24 bytes |
| Configuration |
TwinCAT (M-Bus function blocks) |
| Nominal voltage |
24 V DC (-15 %/+20 %) |
| Input voltage |
24 V DC (-15 %/+20 %) |
| Special features |
connection of up to 40 M-Bus devices; TwinCAT library available |
| Weight |
approx. 60 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Approvals |
CE, UL |
 |
 |